Systemair katalog - page 64

64
|
Variable air volume controllers
Technical data
Electrical data
Power supply
AC 24V, 50/60 Hz, DC 24V (from actuator)
Operating range
AC 19.2 ... 28.8V/DC 21.6 ... 28.8V
Power
consumption
Operation
Dimensioning
1 W
2 VA
Connection
Socket for Belimo PP connection, RJ12
Connecting cable
see «Connection»
Interface
Communication
Point to Point (PP), no bus mode (MP)
Supported devices
Belimo actuator/VAV controller
with PP/MP connection, see «Supported devices»,
Scope of function dependent on type of device
Operating
LCD display
2 x 16 characters, with background illumination
Keys
⇩ / ⇧ / – / + / OK
Quick start guide
enclosed stickers, de/en
Safety
Protection class
III
Safety extra-low voltage
Electromagnetic compatibility
CE in accordance with 2004/108/EC
Operating temperature
0 ... 50°C, non-condensing
Non-operating temperature
–20 ... 50°C, non-condensing
Dimensions / Weight
Dimensions
L x W x D: 85 x 65 x 23 mm
Weight
Approx. 260 g
ZTH-ZEN
Service-Tool for parameterisable and communicative Belimo actuators
and VAV controllers. Connection via service socket on the device or
MP/PP connection.
Information
Belimo Automation AG reserves the right to implement supplements, changes and
improvements at any time, i.e. without prior notification. See
for current
• version overview,
• release information,
• most up-to-date operating instruction, etc.
Supported devices
Damper product range
..-MF / ..-MP / ..-MFT(2) / ..LON
Valve product range
..-MF / ..-MP / ..-MFT(2) / ..LON
EPIV – pressure-independent
characterised control valve
P6..W..-C24E
available starting 2011
Fire damper actuator
BF-TopLine with BKN230-24MP
VAV product range
VRD2 / VRD2-L
available 1992-2007
VRD3
available starting 2008
VRP-M (VAV and STP applications)
available starting 2005
NMV-D2..
available 1992 to 2000
LMV-D2M / NMV-D2M..
available 2000 to 2006
LMV-D2-MP / NMV-D2-MP / SMV-D2-MP.., LHV-D2-MP..
available 2006 to 2011
LMV-D2LON / NMV-D2LON
available 2006 to 2011
LMV-D3-MP / NMV-D3-MP / SMV-D3-MP.., LHV-D3-MP..
available starting 2011
LMV-D3LON / NMV-D3LON
available starting 2011
Safety notes
!
• The device must not be used outside the specified field of application, especially not in
aircraft or in any other airborne means of transport.
• Connection permitted only to Belimo devices with 24V safety extra-low voltage and PP/
MP interface.
• Changes of parameters, etc. may not be performed except after consultation/specification
of the OEM, device or mechanical/electrical contractor. Operating and adjustment
regulations must be observed.
1...,54,55,56,57,58,59,60,61,62,63 65,66,67,68,69,70,71,72,73,74,...87